Isaias Ramirez, Ramiro Hernandez,
and Gerardo Montoya
Instituto de Investigaciones Eléctricas
Cuernavaca, México 62490
| One of the main reasons for using
nonceramic insulators in polluted regions
is the reduction of maintenance
needed to keep a line in service. Because
the useful lifetime of these insulators
depends largely on the pollution
conditions, it is advisable to
inspect the insulators on a regular
cycle. The article discusses several
diagnostic techniques that can be applied
to detect risky conditions before
failure. |
Introduction: Insulator pollution is one of the main problems with insulators
on transmission lines and in substations. Utilities annually
budget and allocate considerable resources for preventive
and corrective maintenance to minimize system interruptions.
Several methods are being used to predict the operative conditions
of the insulation, such as the detection of visual corona on
insulators, measurements of the equivalent salt deposit density
(ESDD), and nonsoluble deposit density (NSDD), and measurement
of the electric field along insulators [1]–[4]. In Mexico,
because of weak regulations, the pollution level has increased in
recent years and the placement of heavy industries close to the
overhead power system is a further cause of pollution.
The use of nonceramic insulators is preferred by most of the
utilities in Mexico; however, manufacturers do not recommend
preventive maintenance. Nevertheless, in highly polluted areas
utilities must perform preventative maintenance, otherwise system
outages will occur. Some nonceramic insulators are being
used in highly polluted areas but tracking and erosion on these
insulators has limited their use in these regions. Sometimes
with a better selection in the characteristics of the insulation, the
problem can be successfully overcome; however, there is a risk
of insulation over-dimensioning. This reselection is achieved
with more leakage or arcing distance, redesigning the profile,
and with the use of different matrix insulating material such as
silicone rubber. Although nonceramic insulators have better
performance than traditional insulators under polluted conditions,
their expected life span, and their long term reliability, are
still unknown.
Nonceramic insulators have been installed since 1995 on
transmission lines located in polluted regions along the coast of
the Pacific Ocean in the state of Michoacán, México. In addition
to marine pollution, this area is home to steel and fertilizer
industries. Pollutants from these industries are dispersed to the
transmission lines that supply power to them. In these areas,
visual inspections of these insulators have been performed periodically
during the night for signs of surface discharges. As the
determination of the operative condition is difficult to establish
based on the presence or absence of surface discharges on the
insulators, leakage current monitoring was implemented on two
towers. Although the insulators performed well for two years, in 1998, the sensors detected leakage current peak values between
350 to 450 mA on various insulators. These insulators were
examined and it was determined that they displayed critical degradation
along their surface, consisting of tracking and erosion.
The degraded nonceramic insulators were replaced by new ones
because they represented a risk of failure of the power line. The
newly installed insulators were redesigned by the manufacturer
with more weathersheds and leakage distance added. Currently,
these insulators continue to operate on the transmission line.
Since 2003, visual corona and electric field measurements
were added as diagnostics of the insulators in service to identify
insulators at risk. Also, ESDD, NSDD, and leakage current
measurements continue to be used as diagnostics and this article
presents the results of these evaluations.
| Table 1.Characteristics of Nonceramic Insulators Installed. |
| Insulator |
Housing material |
Sheds |
Unified specific
creepage distance(mm/kVp-p) |
Arcing distance
(mm) |
Length (mm) |
| NCI-1 |
SiR |
63 |
40.0 |
2234 |
2591 |
| NCI-2 |
SiR |
48 |
28.5 |
2240 |
2591 |
| NCI-3 |
EPDM/SiR |
60 |
35.8 |
2310 |
2591 |
Pollution Level and Leakage Current
The insulators installed on a 230-kV line in polluted regions
along the coast in the state of Michoacán are characterized by
the data in Table 1. The line operates at a maximum of 245
kV phase-to-phase and this voltage is used for calculating the
unified specific creepage distance (mm/kVp-p) as per IEC 60815
[5]. The housing materials SiR and EPDM/SiR corresponds to
silicone and a blend of EPDM and silicone rubbers, respectively.
Insulators on two structures in the region of highest pollution
level were monitored for leakage current, using custom made
monitors installed on the ground side of the insulators [6], in
which the number and magnitude of leakage current peaks are
logged.
After only one year, insulator NCI-1 had ESDD values between
0.91 to 1.82 mg/cm2 and a NSDD of 2.56 to 8.05 mg/cm2.
The ESDD measurements that were done 2 years after the initial
installation of the insulators showed pollution levels from 0.45
to 0.55 mg/cm2. Correspondingly, the magnitude of the leakage
current increased with increasing ESDD level as shown in
Figure 1. After 8 years, the pollution level actually decreased to
0.1 mg/cm2, which was attributed to reduced production levels
from the nearby industries.
Salt-fog tests at 14 and 112 kg/m3 and clean fog tests were
done on insulators removed after 8, 18, 25, 36 and 45 months of
service. These results are shown in Figure 2. From the measurements
of ESDD, it was verified that the flashover voltage was
lower when the ESDD and the corresponding leakage current
measurements were lower.
 |
 |
Figure 1. Leakage current measured on two towers in the most
severe area along the 230-kV line. |
Figure 2. Flashover of insulators removed from the line after 8,
18, 25, 36 and 45 months and tested in the laboratory using the
salt-fog and clean-fog tests. |
Corona Inspection
The first corona inspection, which was carried out in 2003,
using a DayCor II corona camera [7], showed no corona on any
of the transmission line insulators. However, the inspection during
2004 showed corona around the high voltage end. During
the inspection of 2004, corona activity was observed around the
high voltage end of type NC-2 and NCI-3 insulators as shown in
Figure 3. No corona was evident on type NC-1 insulators.
In 2006, the inspection identified corona activity on the same
insulators, as shown in Figure 4. In addition, corona was detected
near the energized side on 12 other insulators, and on at the
grounded end on another insulator. These observations could
be attributed to either the position or absence of corona rings
while in most of the cases, corrosion of the hardware caused displacement
of the grading ring. Because damage to the insulator
housing is a distinct possibility over the long term, grading rings
were either added or replaced.
Figure 3. Corona inspection of nonceramic insulators in 2004.

Figure 4. Corona inspection of nonceramic insulators in 2006.
In-Service Electric Field Measurements
Porcelain material and component manufacturing imperfections including voids can lead to the formation and growth of micro-cracks in the porcelain. Thermal cycling and differential thermal expansion between materials and the applied electrical and mechanical stress grow these cracks, which may develop into carbonised conducting channels between the metal pin and cap. This produces a lower insulation resistance and increased dielectric losses and heating in this disc. Electrical stress is highest near the conductor so it is common for the insulator closest to the conductor to be in a degraded condition. However, degradation also depends strongly on manufacturing imperfections that tend to create stress concentration points, therefore random failures can occur at any position in the string. The composite insulator tester developed by Hydro-Québec
[8] was used to measure the field distribution along the insula-
Table 1. Characteristics of Nonceramic Insulators Installed.
Insulator Housing material Sheds
Unified specific
creepage distance
(mm/kVp-p)
Arcing distance
(mm) Length (mm)
NCI-1 SiR 63 40.0 2234 2591
NCI-2 SiR 48 28.5 2240 2591
NCI-3 EPDM/SiR 60 35.8 2310 2591
Figure 1. Leakage current measured on two towers in the most
severe area along the 230-kV line.
Figure 2. Flashover of insulators removed from the line after 8,
18, 25, 36 and 45 months and tested in the laboratory using the
salt-fog and clean-fog tests.
Authorized licensed use limited to: University of Waterloo. Downloaded on November 22, 2009 at 22:54 from IEEE Xplore. Restrictions apply.
30 IEEE Electrical Insulation Magazine
tors. The field probe of this tester is mounted on a carriage which
must be slid manually along the insulator by a lineman on the
tower. The measured data are stored in the memory of the tester
which is later transferred to a computer and according to the
shape of the curve it may be determined if the insulator is damaged,
because damage is assumed to affect the electric field. An
example of electric field measurement is shown in Figure 5.

Figure 5. Electric field along insulator NCI-3 on phase C1 recorded
in 2003, 2004, and 2006; shed No. 1 is at the tower end
and shed No. 31 is at the line end.
Insulators Removed for Visual Inspection
In 2003, one of insulators, NCI-2 of phase C, was removed
from the transmission line for a close-up inspection of the housing.
The selection was based on the time in service of about 8
years, and because it had the highest variation in the electric
field measurement. The insulator showed slight erosion on the
surface, of about 15 mm in length and 1 mm in depth, and in
different regions along the surface, as shown in Figure 6. As
the risk of failure was considered to be low, the insulator was
put back into service on the same structure. In 2004 the electrical
field measurements, Figure 5, showed an increased variation
near the tower end of the insulator. The same insulator, NCI-2
of phase C, was removed for close-up inspection. The inspection
revealed that the major erosion observed a year earlier had
increased from 15 to 20 mm in length and from 1.0 to 1.5 mm
in depth. Once again, it was judged that the degradation did not represent a high risk of failure and so the insulator was reinstalled
on the same structure.
However in 2006, the electric field distributions presented
major changes along the entire

Figure 6. Visual inspection of insulator NCI-2 of phase C carried out in 2003.

Figure 7. Severe erosion near the line end observed in 2006 on insulators NCI-2 and NCI-3.
length of the insulator, when
compared to the previously measured field distribution, and as
evident for insulator NCI-3 in Figure 5. Three insulators, NCI-2
on phase C and NCI-3 on phase C1 and C2, were removed and
showed severe degradation as shown in Figure 7.
Insulators NCI-3 on phases C1 and C2 had been in service for
6 years, with degradation exposing the fiberglass rod. Because
this condition could quickly lead to a catastrophic failure, these
insulators were changed out for new units. Insulator NCI-2 on
phase C, with 10 years of service, showed very deep erosion on
its sheath near to the energized end of the insulator. As the depth
of the erosion was about 2 mm, and approaching the core, this
insulator was also changed out with a new unit.
In the same year, insulator NCI-1 on phase B was also removed
from service to validate the results obtained during the
previous two inspections, which indicated that its operational condition was satisfactory. The examination showed only minimal
erosion along the length of the insulator and the insulator
was re-installed.
 |
 |
Figure 8. Simulated normal component of the electric field, 0.5
mm above the surface of the housing, on insulator NCI-2, with
corona ring; from tower to line end in the figure. |
Figure 9. Simulated normal component of the electric field, 0.5
mm above the surface of the housing, on insulator NCI-2, with
corona ring, and with a layer of pollutant having a conductivity
of 1 × 10-6 S/m; from tower to line end in the figure. |
Simulation of Electric Field
As a comparison to the in-service electric field measurements,
the electric field distribution of the insulators was modeled using
COMSOL Multiphysics, without pollution, and with a surface
layer of pollutant having a conductivity of 1 × 10-6 S/m.
Figure 8 shows that the simulated normal component of the
electric field on insulator NCI-2, without considering pollution
and with line end corona ring, is quite low over most of the insulator,
increasing slightly near to the tower end of the insulator,
but increasing exponentially between the first shed and the end
fitting at the line end. However, the normal component of the
electric field at the line end hardware seal is only 1.8 kV/cm,
which is considerably lower than the 4.5 kV/cm maximum electric
field for non-ceramic insulators that has been suggested in
an IEEE Committee paper by Phillips et al. [9].
Pollution is simulated by including a uniform and continuous
layer of conductivity of 1 × 10-6 S/m over the surface of the insulator.
This simulation, shown in Figure 9, indicates that the normal
component of the electric field follows the simulated result
without pollution; the maximum electric field is somewhat higher
at 3.9 kV/cm, but is still lower than the suggested maximum.
However, with this electric field strength, slight degradation can
take place on the insulator surface. This simulated electric field
value suggests that as the pollution conductivity increases, the
degradation will also increase.
Conclusions
Based on periodic inspections that were made in this project,
degradation of nonceramic insulators may be detected using a combination of techniques such as measurement of ESDD and
leakage current, corona observations, and measurement of the
electric field. Corona was evident on insulators that either did
not have a corona ring or had a ring that was not in the correct
position, and in this project, corona became evident on corona
rings that had shifted because of corrosion of the mounting hardware.
In addition, it is possible to establish degradation of an
insulator by measurement of the electric field. Simulation of
the electric field on the insulators that were used in this project
suggests that the current suggested maximum electric field on
insulators, 4.5 kV/cm, may still be too high; however, it is still
too early to say definitively that this level should be lower.
The results of this project indicate that the useful life of nonceramic
insulators installed in polluted regions depends largely
on the actual conditions of pollution. From earlier experience on
this transmission line, some insulators showed severe degradation
in less than one year, while others have endured 4 years
and still others have been operating for 10 years without any
problems
One of the main reasons for using nonceramic insulators in
polluted regions is the reduction of maintenance that otherwise
would be necessary to keep a line in service. Because the useful
lifetime of these insulators depends largely on the pollution
conditions where the insulators are operating, it is advisable to
inspect the insulators on a regular cycle. These inspections will
help detect insulators at risk of failing and help maintain the reliability
of an overhead line.
Acknowledgment
The authors would like to thank the personnel from STyT
Lázaro Cárdenas and from CFE-CTT for their invaluable help
in this project.
References
[1] G. Montoya-Tena, R. Hernández-Corona, and I. Ramírez Vázquez, “Experiences
on pollution level measurement in Mexico,” Electr. Power Syst.
Res., vol. 76, pp. 58–66, 2005.
[2] R. Hackam, “Outdoor HV composite polymeric insulators,” IEEE Trans.
Dielectr. Electr. Insul., vol. 6, pp. 557–585, 1999.
[3] R. S. Gorur, E. A. Cherney, and J. T. Burnham, Outdoor Insulators. Phoenix,
AZ: Ravi S. Gorur, Inc., 1999, pp. 131–144.
[4] Working Group 22.03: Insulators, “Review of in service diagnostic testing
of composite insulators,” Electra, no. 169, pp. 105–119, 1996.
[5] Guide for the Selection of Insulators in Respect of Polluted Conditions,
IEC 60815, 1986.
[6] J. L., Fierro-Chavez, I. Ramirez-Vazquez, and G. Montoya-Tena, “Online
leakage current monitoring of 400 kV insulator string in polluted areas,”
in IEE Proc. Gener., Transm. Distrib., vol. 143, no. 6, pp. 560–564,
Nov. 1996.
[7] M. Linders, S. Elstein, P. Linders, J. M Topaz, and A. J. Phillips, “Daylight
corona discharge imager,” in 11th Int. Symp. High Voltage Engineering,
vol. 4, pp. 439–443, 1999.
[8] G. H. Vaillancourt, S. Carignan, and C. Jean, “Experience with the detection
of faulty composite insulators on high-voltage power lines by the
electric field measurement method,” IEEE Trans. Power Del., vol. 13, no.
2, pp. 661–666, 1998.
[9] IEEE Task Force on Electric Fields and Composite Insulators, “Electric
fields on ac composite transmission line insulators,” IEEE Trans. Power
Del., vol. 23, no. 2, pp. 823–830, 2008.
Isaias Ramirez-Vazquez received the
B.S. degree from the Facultad de Ingeniería
Mecánica Eléctrica y Electrónica
(FIMEE), Salamanca, Gto, México, in
1990 and the M.S. degree from FIMEE in
1999. He is currently working toward the
Ph.D. degree at the University of Waterloo,
Ontario, Canada. He is a researcher in
the Instituto de Investigaciones Eléctricas
en Cuernavaca, Morelos, México. His current research interests
include outdoor insulation, insulation coordination, and electromagnetic
transients in power systems.
Ramiro Hernández-Corona was born in
Cuernavaca, Morelos, México, on September
17, 1966. He received the B.S. degree
in electrical engineering from the University
of Morelos in 1991. In the same year,
he joined the Instituto de Investigaciones
Eléctricas (Electrical Research Institute)
located in Cuernavaca, Morelos, México.
In 1995, he received a Master’s degree in
electrical engineering from the University of Salford, UK. He
is currently a researcher of the Transmission and Distribution
Department. He has been working in activities related to pollution
flashover on external insulation and of lightning protection
in transmission and distribution lines.
Gerardo Montoya-Tena was born in
México City, México, on April 27, 1962.
He received the B.S. degree in electronic
and communications engineering from the
Instituto Politécnico Nacional (National
Polytechnic Institute). In 1990, he received
with honors a Master’s degree in electrical
engineering from the Universidad Nacional
Autónoma de México (Autonomous National
University of Mexico). In 1986, he joined the Instituto de
Investigaciones Eléctricas (Electrical Research Institute) located
in Cuernavaca, Morelos, México. He is currently a researcher of
the Transmission and Distribution Department. He is author of
several papers about external insulation and overhead transmission
lines. He has been working in activities related to pollution
flashover on external insulation in transmission and distribution
lines. He is member of specialists committee of the Mexican
utility.
download the pdf