765 kV EHV Transmission: Power Highways Supporting Grid Expansion and Energy Transition

< Back to Articles & Case Studies
Partial Discharge background

As power systems worldwide scale to meet unprecedented demand, from electrification and industrial growth to hyperscale data centers and large-scale renewables – 765 kV extra-high-voltage (EHV) AC transmission lines are increasingly considered in long-term transmission planning. These “power highways” move massive blocks of electricity over long distances with fewer circuits, lower losses, and improved overall system efficiency.

 

What are 765 kV lines?

Operating among the highest AC transmission voltages in commercial service, 765 kV lines are typically built as overhead systems using tall steel lattice towers (about 130–180 ft) with long spans that can reach roughly 1,400 ft. A single 765 kV circuit can transmit the equivalent power of three 500 kV lines or up to six 345 kV single circuits, dramatically increasing power density per corridor and reducing the need for multiple parallel rights-of-way.

 

Where are they used?

Large-scale 735/765 kV networks have been in service for decades in Québec (Canada) and across parts of the United States, particularly in systems originally developed by major utilities such as AEP and NYPA. Globally, similar voltage classes (often referred to as ~750–787 kV) have been deployed in Brazil, Venezuela, South Africa, South Korea, India, Japan, and across regions of the former USSR forming long-distance corridors linking major generation centers to load hubs.

 

Why utilities invest in 765 kV

The primary driver is simple physics and economics: transmitting large power blocks over hundreds of kilometers at very high voltage significantly reduces I²R losses and minimizes land use compared with multiple lower-voltage lines. Today, 765 kV backbones are increasingly considered to:

  • Integrate remote renewable generation at scale.
  • Support rapid growth of data centers and industrial loads.
  • Relieve congestion on existing 345–500 kV networks.
  • Improve grid resilience by offloading stressed lower-voltage corridors.

 

In many long-term grid plans, 765 kV acts as a high-capacity overlay that strengthens the entire transmission system beneath it.

 

The Technical Reality at 765 kV: Corona and Insulation Take Center Stage

At these voltage levels, corona discharge and insulation design are no longer secondary concerns – they are central technical constraints that shape every aspect of the line.

 

Corona-related challenges:

 

High electric field stress and corona onset

At 765 kV, surface electric fields on conductors, clamps, and fittings can easily exceed air ionization thresholds. Even small geometric irregularities may trigger corona, leading to:

  • Corona power losses (kW per km).
  • Audible noise and visible glow.
  • Ozone and nitrogen oxides generation.
  • Radio and TV interference that must remain within regulatory limits.

 

Hardware design and aging under corona

To control these effects, connectors, clamps, grading rings, and end fittings require meticulous shaping—often validated through advanced 3D electric-field simulations and laboratory testing. If corona is not fully suppressed, especially on polymer or composite components, accelerated aging and degradation can occur, ultimately reducing insulation life and increasing maintenance costs.

 

Insulation and clearance challenges:

  • Air clearances and insulation coordination – Insulation coordination at 765 kV demands very large phase-to-phase and phase-to-structure clearances to withstand lightning and switching overvoltages with adequate safety margins. Utilities frequently specify design criteria beyond minimum codes, resulting in physically larger towers, substations, and buswork—all contributing to higher CAPEX.
  • Insulators, pollution, and icing – Long insulator strings or tall post stacks with optimized shed profiles are required to achieve sufficient creepage distance under pollution, wetting, or icing conditions. Grading and corona rings are essential to control voltage distribution and local electric fields. In harsh environments, selecting and maintaining these insulation systems becomes increasingly complex at 765 kV.

 

System-Level Implications: Cost, Complexity, and the Need for Advanced Diagnostics

Operating at 765 kV creates a challenging electromagnetic environment along the right-of-way. Corona-related noise and interference tend to worsen over time as conductors age and surface conditions degrade. This reality drives design choices such as bundled conductors, larger bundle spacing, and extensive use of grading hardware.

From a lifecycle perspective, the cost and complexity of 765 kV assets make proactive inspection and condition-based maintenance essential. Any surface damage, contamination, or hardware modification can reintroduce corona and erode carefully designed insulation margins.

This is where advanced diagnostic tools become critical. Non-contact inspection technologies such as solar-blind UV imaging enable utilities to detect and precisely locate corona and partial discharge activity from a safe distance, even in daylight conditions. Early identification of abnormal corona allows corrective action before minor surface issues escalate into insulation failures, outages, or regulatory complaints.

 

Commissioning at 765 kV: Verifying Corona Performance at Initial Energization

The commissioning phase is the first opportunity to evaluate how a 765 kV transmission system performs under real electrical stress conditions. At this stage, theoretical design margins and construction quality are tested against operating voltages approaching the limits of air insulation. Due to the extremely high electric fields involved, even small deviations in geometry, surface condition, or hardware installation can give rise to corona or partial discharge activity that is not detectable through conventional visual inspection methods.

 

During commissioning, solar-blind ultraviolet (UV) inspection serves as a critical validation tool for identifying corona and partial discharge activity that may not be apparent through standard visual or electrical tests. At 765 kV, defects related to design tolerances, manufacturing variability, transport damage, or installation errors such as misaligned fittings, missing or improperly installed grading rings, or damaged spacers can become active discharge sites once voltage is applied. Non-contact UV scanning allows utilities and EPC teams to directly visualize and localize these sources of electrical stress, enabling corrective action before the asset enters continuous operation and while contractual and warranty responsibilities are still clearly defined.

 

Beyond resolving immediate commissioning findings, UV inspections performed at initial energization establish a clean and reliable baseline of corona performance for each asset. This baseline provides a reference against which future inspections can be compared, supporting condition-based maintenance and early detection of emerging degradation. When incorporated into digital inspection and asset-management workflows, commissioning-time UV data forms the foundation for long-term performance monitoring, risk prioritization, and lifecycle management of high-value 765 kV transmission infrastructure.

 

Looking Ahead

Although 765 kV transmission projects involve significant capital investment and complex planning and permitting processes, they continue to be considered by utilities as part of long-term strategies for bulk power transfer, grid reinforcement, and integration of large-scale generation. As transmission systems expand while portions of the existing EHV infrastructure age, maintaining reliable operation at these voltage levels increasingly depends on both robust design practices and effective condition monitoring throughout the asset lifecycle.

 

At 765 kV, corona activity and insulation performance are key technical factors influencing power losses, electromagnetic interference, environmental impact, and long-term asset reliability. For this reason, many utilities supplement conventional maintenance programs with condition-based inspection approaches. Non-contact diagnostic techniques, including solar-blind ultraviolet imaging, allow daylight detection and localization of corona and partial discharge activity on conductors, fittings, and insulation hardware. When incorporated into routine inspection and asset-management workflows, such tools support early identification of abnormal conditions, trending over time, and more informed maintenance prioritization for EHV transmission assets.

 

 

 

 

Contact
















    Schedule a meeting

    Send

    DOWNLOAD PRODUCT CATALOG









      Please fill in your details,
      and we'll send you a link to the webinar








        Rotating Machines Course

          Electrical Utilities Course

            Fill the form to view the webinar








              REQUEST FULL SPEC-SHEET

               








                REQUEST FULL SPEC-SHEET

                 









                  REQUEST FULL SPEC-SHEET

                   









                    REQUEST FULL SPEC-SHEET

                     









                      REQUEST FULL SPEC-SHEET

                       









                        REQUEST FULL SPEC-SHEET

                         









                          REQUEST INSPECTION PRODUCTS

                           









                            REQUEST FULL SPEC-SHEET